Skip to main content
ElecSimHub

Plant owner: start here

Three inputs, then you see what the engine really computes: output of a typical day, peak power and capacity factor — plus payback when you give a price and a cost.

Photovoltaic

Shading loss & hot-spot risk, multi-MPPT mismatch, LVRT ride-through, P-Q capability envelope, PV power quality, active anti-islanding detection, PV short-circuit contribution and the DC-side cable check.

Step 1 of 3Photovoltaic

Pick a scheme first — then this column can calculate

This column runs the real engine on your project scheme, and there is none yet — that is why no calculation buttons are shown here (they are not broken). Start with any of the ways below; the fastest is the built-in example (one click, real parameters).

Two ways in — pick either one

The studies in this column normally run on a whole scheme. If you only need one calculator-type function, you do not have to build a scheme.

① Load a real example scheme (fastest)

10 kV incoming (200 MVA short-circuit level) → 1250 kVA transformer (Dyn11) → LV main switchboard → busbar → 5 feeders plus a fire/emergency ATS branch. 1000 kW calculated load, cosφ 0.85, power-factor target 0.95.

Load the real example scheme and start calculating →

The scheme and its parameters go straight into your browser; replace the data with your own at any time.

② Do not load a scheme — just type the numbers (calculator mode)

Calculator mode computes the few outputs that only depend on parameters you type in yourself. Anything that genuinely needs the whole system (full-network load flow, coupling with other devices) is shown as “needs a scheme” and no number is given.

Nothing is pre-filled and nothing is invented: leave a required field empty and the result area says “unavailable”.

③ Or build your own scheme

In the studio, place devices, wire them and pick models — that becomes your project scheme (drawings / BOM / report can be exported).

Open the studio →
Need a hand?

Use the chat bubble bottom-right, or Contact us — we will set the example to your site parameters.

Note: every number comes from the engine. With no scheme, nothing is invented here.

New-energy topics: what to specify, how it is checked, what usually goes wrong

One card per domain — PV, wind, storage, micro-hydro and wind–solar–storage hybrids. Each card names the audience, the parameters that decide the selection, the calculation basis, the common pitfalls, and the page of the simulator that carries the numbers. Values the engine does not return yet are labelled "to be wired" and are never estimated here.

  • Audience:
  • buyers / owners
  • design institutes / electrical engineers

Photovoltaic (PV) plants

to be wired

Audience

Buyers and owners sizing a PV plant; design engineers checking the DC side and the point of connection.

Selection parameters

Module Voc/Vmp including the low-temperature voltage rise; MPPT count and string length; DC cable cross-section and voltage drop; inverter P–Q capability and reactive headroom; short-circuit contribution at the point of connection.

Basis and assumptions

Irradiance-and-temperature model (IEC 61853) on a typical meteorological year; the engine returns one 24-point typical day, not 8760 hourly steps, and the annual figure is that day scaled to 365 — this is stated on the page.

Common pitfalls

Sizing DC cables on nameplate current and ignoring the Voc rise at the lowest ambient temperature; treating shading loss as a single-string loss while mismatch spreads across the array; using the wrong edition of the LVRT curve.

Where the numbers come from

Shading, hot-spot risk, multi-MPPT mismatch, LVRT, the P–Q envelope, power quality, anti-islanding, inverter short-circuit contribution and the DC-side check run on /pv; yield, peak and payback come from the owner quick estimate on the same page (engine study pvTimeSeries).

To be wired

PV string designer, mounting tilt and row spacing, and solar pumping have no engine study yet and are marked "to be wired" on the page.

  • pv-string-designer
  • pv-mounting-tilt-spacing-calculator
  • solar-pumping
  • pv-cable-voltage-drop-calculator
  • solar-yield-payback-calculator

Every figure the simulator shows is returned by the calculation engine on that page; this guide is not a substitute for it. Items marked "to be wired" have no engine source yet and are shown as such instead of being estimated.

Definitions, units and why the number matters for selection and quotation. Searchable, grouped by topic, collapsed by default.

Every ? mark on this page opens the same explanation in place — no page change.

13 term(s) shown of 13

Short circuit & protection · 1
Ik[kA (rms)]Short circuit & protection

Initial symmetrical short-circuit current at the fault point (IEC 60909-0): the rms current the network drives into a bolted three-phase fault, with the voltage source replaced by the c·Un/√3 equivalent.

Why it matters: It is the number every device rating is compared with — Icw, breaking capacity and the cable thermal check all read against Ik. Under-estimate Ik and the panel you quote will be destroyed on the first fault; over-estimate it and the client pays for switchgear he does not need.

Transformers & switchgear · 1
uk%[% (referred to rated current and the reference temperature)]Transformers & switchgear

Short-circuit impedance voltage of a transformer: the primary voltage, in percent of rated voltage, that drives rated current through the short-circuited secondary winding (IEC 60076-1).

Why it matters: It fixes the LV fault level (approximately I″k ≈ In / uk) and at the same time the voltage drop under load. This is a real quotation trade-off: a larger uk lowers the fault level (cheaper switchgear downstream) but increases voltage drop and losses. Always quote uk together with the transformer rating.

Power quality & grid connection · 5
PCC[location (no unit)]Power quality & grid connection

Point of common coupling (PCC): the interface in the network where the customer installation and the utility network are coupled, and therefore where the connection conditions apply.

Why it matters: It defines what the utility may complain about and what you must prove: voltage band, harmonic distortion, flicker and voltage-dip behaviour are all specified at the PCC, not at the equipment terminals. Studies or measurements made somewhere else do not demonstrate compliance.

THDu[%]Power quality & grid connection

Voltage total harmonic distortion THDu = √(Σ Uh²) / U1 × 100 %, measured as required by IEC 61000-4-7.

Why it matters: It is the quantity a grid code or a utility limits at the point of common coupling (for reference: IEEE 519 sets 5 % THDv at the PCC, IEC 61000-2-2 gives 8 % for LV class 2). Exceeding it means filters, detuned banks or a larger transformer — a cost that appears only if the study is done before the order.

THDi[%]Power quality & grid connection

Current total harmonic distortion THDi = √(Σ Ih²) / I1 × 100 %: the harmonic content of the load current relative to its fundamental.

Why it matters: It is what sizes harmonic filters and detuning reactors and what drives cable and transformer derating. IEEE 519 limits it as a function of the ratio between the short-circuit current and the load current — so THDi is meaningless for a quotation unless the fault level is quoted with it.

cos φ[dimensionless (0–1)]Power quality & grid connection

Power factor cos φ: the ratio of active power to apparent power (displacement factor between voltage and current), with the distortion factor included when the current is distorted.

Why it matters: It sets the kVA that the transformer, generator or supply contract must provide for a given kW, and it is contractual: a low power factor triggers penalty charges or a mandatory compensation bank. It is therefore both a design input and a line in the price.

Qc[kvar]Power quality & grid connection

Reactive compensation rating Qc: the output of the capacitor bank, sized as Qc = P × (tan φ1 − tan φ2) to move the installation from its present to its target power factor.

Why it matters: It is the item being quoted, and its usable output drops in a harmonic-rich network unless a detuned (reactor-protected) bank is used. The target power factor is a customer input, not a default — quoting a bank without stating the target pf is not a complete offer.

Stability & storage · 5
CF[%]Stability & storage

Capacity factor: the energy actually produced over a period divided by the energy the plant would have produced running at its rated power for the whole period (for PV this is dominated by irradiance and temperature, not by the inverter).

Why it matters: It is the number that converts a nameplate kWp into annual kWh, and therefore into revenue and payback. A quotation that gives only the kWp figure does not say what the plant will actually deliver — ask for the assumed capacity factor.

LVRT[defined by a voltage (pu) / time (s) curve]Stability & storage

Low-voltage ride-through: the duty (and the capability) of a generator or inverter to remain connected while the voltage at the PCC dips along a specified voltage-versus-time profile, instead of tripping off.

Why it matters: It is a grid-connection condition in most markets: a plant that cannot ride through the required curve cannot be connected or must be retrofitted. Confirm the required LVRT curve before sizing the inverters, because it decides the hardware class.

SOC[%]Stability & storage

State of charge of a battery or BESS: the remaining energy as a percentage of the rated (or usable) capacity.

Why it matters: It bounds what the storage can deliver at any instant, so it drives the protection settings, the dispatch strategy and the delivered-energy guarantee. A quoted availability figure is meaningless unless the SOC window it assumes is stated.

DOD[%]Stability & storage

Depth of discharge: the complement of the state of charge — how much of the capacity is cycled out, normally quoted as a maximum in cycle-life specifications.

Why it matters: It is the trade between usable capacity and battery life: the same nominal kWh quoted at 80 % DOD delivers fewer cycles than one quoted at 60 %. Because it changes both the usable kWh and the replacement date, the DOD must be on the datasheet next to the price.

RTE[%]Stability & storage

Round-trip efficiency of a storage system: the energy returned during discharge divided by the energy absorbed during charge over a complete cycle.

Why it matters: It decides how much of the energy you pay for actually comes back out, and therefore the real cost per delivered kWh. Watch the boundary of the figure (DC-DC looks much better than AC-AC) — comparing two offers on different boundaries is a common source of wrong quotations.

System & general · 1
Payback[years]System & general

Simple payback period: the capital cost divided by the annual net saving, without discounting or price escalation (a screening figure, not a financial model).

Why it matters: It is the number that decides whether the customer buys now. Because it is a simple ratio, the two inputs that drive it (energy price and unit capex) must be shown next to it — otherwise nobody can tell which assumption the figure stands on.