ElecSimHub

Short-circuit calculation & electrical safety check

A quick-reference case: one upstream source feeding an LV busbar through one transformer. For complex topology, multiple fault locations and equipment checking use the scheme page /shortcircuit.

Method

Enter the upstream short-circuit capacity S″kQ and the transformer nameplate data. The equivalent voltage source method of {p1} gives the initial symmetrical short-circuit current I″k, the peak short-circuit current ip, the breaking current Ib and the loop impedance Zk. Anything the input does not support is shown as not available - never as zero.

Input sources

User input

Nameplate and system data entered by you.

Standard basis

The c factor and formulas follow the selected standard

Engine result

Input and calculation

Enter the data under each group and press Calculate; no request is sent until the required fields are complete.

Standard basis
Standard selectable: IEC / GB / EN / GOST; equivalent voltage source method (GB/T 15544.1 is a modified adoption of IEC 60909-0, same c factor).

Upstream grid

Required
kV
Range
Positive number
Default source
Example value, editable
Required
MVA
Range
Positive number
Default source
Example value, editable
Optional
Range
Positive number; may be left empty
Default source
No default
If left empty the engine uses its default R/X convention; the source is stated in the result.

Transformer and LV busbar

Required
kVA
Range
Positive number
Default source
Example value, editable
Required
%
Range
Positive number
Default source
Example value, editable
Recommended
kV
Range
Positive number; may be left empty
Default source
Example value, editable
Optional
Range
Positive number; may be left empty
Default source
No default
If left empty the engine uses its default breaking time; the source is stated in the result.

Required fields complete — ready to run.

Results

Not calculated yet — fill in the inputs on the left, press Run; the results appear here.

Basis and limits

IEC 60909-0, equivalent voltage source method: I″k = c·Un/(√3·Zk); peak ip = κ·√2·I″k with κ = 1.02 + 0.98·e^(−3·R/X); breaking current Ib = μ·q·I″k with the DC time constant τ = (X/R)/(2πf).

Voltage factor c (IEC 60909-0 Table 1): 1.10 (maximum) / 1.00 (minimum) for Un above 1 kV, 1.05 (maximum) / 0.95 (minimum) for Un up to 1 kV.

Grid equivalent impedance Z_Q = Un²/S″kQ referred to the fault side; in the platform default convention c is not folded into Z_Q but applied once in the current equation.

Transformer impedance Z_T = (uk/100)·Un²/Sn referred to the LV side. uk is a required input — a typical dry-type or oil-immersed value is not substituted.

All values are computed by the engine using the selected standard equivalent voltage source method; this page only submits your input and presents the result.

Sample case: MV grid 10 kV / S″kQ = 500 MVA, transformer 1000 kVA / uk = 6 % / Dyn11, LV busbar 0.4 kV, no outgoing cable, no motor load. Hand check: Z_Q = 10²/500 = 0.2 Ω, Z_T = 0.06·0.4²/1 = 0.0096 Ω, Zk = 0.00992 Ω; with c = 1.05 (LV) I″k = 1.05·0.4/(√3·0.00992) = 24.44 kA.

Frequently asked questions
What can this calculator do?
Enter the upstream short-circuit capacity S″kQ and the transformer nameplate data Sn and uk. The IEC 60909-0 equivalent voltage source method returns the initial symmetrical short-circuit current I″k, the peak short-circuit current ip, the breaking current Ib, the short-circuit capacity S″k and the loop impedance Zk, with the c factor, the peak factor κ and the d.c. time constant stated on the page. Typical uses: a quick fault level for switchgear and cable thermal-duty shortlisting, checking a transformer against the rating of the downstream equipment, and a first estimate before a full network study. A value the input cannot support is shown as not available, never as zero.
What is computed, and by which method?
The equivalent voltage source method of IEC 60909-0: the source impedance comes from the upstream short-circuit capacity S″kQ, the transformer impedance from Sn and uk referred to the LV side, and I″k = c·Un/(√3·Zk). The peak factor κ and the d.c. time constant τ come from the R/X ratio of that loop, and ip = κ·√2·I″k.
When is this page not enough?
It is a preliminary estimate on a single equivalent source. The maximum and minimum operating modes of IEC 60909-0 — the far-from-generator and near-to-generator cases — and multi-source superposition need a complete network topology, so for a real protection study open the scheme-based simulator column instead of extrapolating this figure.