Nameplate and system data entered by you.
Short-circuit calculation & electrical safety check
A quick-reference case: one upstream source feeding an LV busbar through one transformer. For complex topology, multiple fault locations and equipment checking use the scheme page /shortcircuit.
Enter the upstream short-circuit capacity S″kQ and the transformer nameplate data. The equivalent voltage source method of {p1} gives the initial symmetrical short-circuit current I″k, the peak short-circuit current ip, the breaking current Ib and the loop impedance Zk. Anything the input does not support is shown as not available - never as zero.
Input sources
The c factor and formulas follow the selected standard
Input and calculation
Enter the data under each group and press Calculate; no request is sent until the required fields are complete.
Upstream grid
Transformer and LV busbar
Required fields complete — ready to run.
Results
Not calculated yet — fill in the inputs on the left, press Run; the results appear here.
Basis and limits
IEC 60909-0, equivalent voltage source method: I″k = c·Un/(√3·Zk); peak ip = κ·√2·I″k with κ = 1.02 + 0.98·e^(−3·R/X); breaking current Ib = μ·q·I″k with the DC time constant τ = (X/R)/(2πf).
Voltage factor c (IEC 60909-0 Table 1): 1.10 (maximum) / 1.00 (minimum) for Un above 1 kV, 1.05 (maximum) / 0.95 (minimum) for Un up to 1 kV.
Grid equivalent impedance Z_Q = Un²/S″kQ referred to the fault side; in the platform default convention c is not folded into Z_Q but applied once in the current equation.
Transformer impedance Z_T = (uk/100)·Un²/Sn referred to the LV side. uk is a required input — a typical dry-type or oil-immersed value is not substituted.
All values are computed by the engine using the selected standard equivalent voltage source method; this page only submits your input and presents the result.
Sample case: MV grid 10 kV / S″kQ = 500 MVA, transformer 1000 kVA / uk = 6 % / Dyn11, LV busbar 0.4 kV, no outgoing cable, no motor load. Hand check: Z_Q = 10²/500 = 0.2 Ω, Z_T = 0.06·0.4²/1 = 0.0096 Ω, Zk = 0.00992 Ω; with c = 1.05 (LV) I″k = 1.05·0.4/(√3·0.00992) = 24.44 kA.
Frequently asked questions
- What can this calculator do?
- Enter the upstream short-circuit capacity S″kQ and the transformer nameplate data Sn and uk. The IEC 60909-0 equivalent voltage source method returns the initial symmetrical short-circuit current I″k, the peak short-circuit current ip, the breaking current Ib, the short-circuit capacity S″k and the loop impedance Zk, with the c factor, the peak factor κ and the d.c. time constant stated on the page. Typical uses: a quick fault level for switchgear and cable thermal-duty shortlisting, checking a transformer against the rating of the downstream equipment, and a first estimate before a full network study. A value the input cannot support is shown as not available, never as zero.
- What is computed, and by which method?
- The equivalent voltage source method of IEC 60909-0: the source impedance comes from the upstream short-circuit capacity S″kQ, the transformer impedance from Sn and uk referred to the LV side, and I″k = c·Un/(√3·Zk). The peak factor κ and the d.c. time constant τ come from the R/X ratio of that loop, and ip = κ·√2·I″k.
- When is this page not enough?
- It is a preliminary estimate on a single equivalent source. The maximum and minimum operating modes of IEC 60909-0 — the far-from-generator and near-to-generator cases — and multi-source superposition need a complete network topology, so for a real protection study open the scheme-based simulator column instead of extrapolating this figure.