Insulation coordination calculator — standard method (IEC 60071)

Enter the system voltage, the pollution degree, the site altitude and, if you have it, the surge-arrester residual voltage. The engine looks up the standard insulation level, applies the altitude correction and returns the withstand voltage you need together with the smallest standard level that meets it. Everything is looked up or computed, never assumed.

Three sources,three clear labels

User input

Entered in the project,not verified.

Standard table

Taken from the selected table and its conditions of use,not user input.

Engine-derived

A calculated quantity;it must be tied to an input version;A value that has not been calculated must not be shown as 0.

Input conditions and sources

Voltage and altitude drive the standard-level look-up and the real calculation; the arrester residual voltage is the easiest value to take from the arrester datasheet. Pollution degree is preset to II (the common neutral class under IEC 60815-1 / GB/T 26218.1) and can be changed to I/III/IV for your site - a preset you can edit, not a hidden assumption.

Required
User input
kV
Required
User input
kV
Required
User input
m
Required
User input
Required
User input
kV
Required
User input
kV
Required
User input
kV
Required
User input
kV
Required
User input
Required
User input
kV
Required
User input
Required
User input

Confirm the scope before running

When a field is left blank, the corresponding result is shown as 'not available'.

Scope and boundary

Three different things on one page, please do not mix them: (1) Um to LI/AC is a LOOKUP from the standard tables - the platform builds no levels of its own; (2) the altitude factor Ka and the required-withstand chain are REAL CALCULATIONS, but K_pr, K_c and K_s are your values, not built in; (3) pollution degree to creepage distance and the air clearance are NEEDS-STANDARD-TABLE items and no number is given. This page does not produce U_rp, does not do switching impulse (Um > 72.5 kV), and does not distinguish internal from external insulation beyond the Ka note. Output is a selection/check reference: it is not a type-test conclusion and not a contractual technical agreement; the final insulation level is per the manufacturer parameter sheet and the test report.

Report and delivery entries

Report

Needs a usable run record for the current input, confirmed conditions and basis;unknown and not-executed items must be kept.

Delivery package

Needs a selected report version and a deliverables list;out-of-date results must not be packaged as current deliverables.

Frequently asked questions
What can this calculator do?
Enter the system voltage, the pollution degree, the site altitude and, if you have it, the surge-arrester residual voltage. The calculator looks up the standard insulation level for that system voltage (IEC 60071-1 Table 2, the same values as GB/T 1094.3-2017), applies the altitude correction of IEC 60071-2 Annex H and the arrester coordination ratio, and returns the withstand voltage you need together with the smallest standard level that meets it. Typical uses: fixing the lightning-impulse and power-frequency withstand levels for a substation or a transformer purchase specification, correcting a standard level for a high-altitude site, and checking that the chosen arrester still coordinates with the insulation. Everything is looked up or computed, never assumed.
Which standards are looked up rather than assumed?
Standard insulation levels follow IEC 60071-1 Table 2 (the same values appear in GB/T 1094.3-2017); the rated voltage to Um follows IEC 60038 / GB/T 156-2017; the altitude correction follows IEC 60071-2 Annex H with the exponent m = 1 for power frequency and lightning impulse. The arrester enters through the coordination ratio K_pr.
What does the altitude correction do to the required level?
Above the reference altitude the air is thinner, so a given clearance withstands less and the Annex H correction raises the required withstand voltage — which can push the selection to the next standard step. When you supply the arrester residual voltage it acts through the coordination ratio, so a lower residual voltage can pull the requirement back down.