Industry assumptions — read this before using the numbers
- 1.Standard: IEC 61660-1:1997 (+Corrigenda 1:1999, 2:2000) — Calculation of short-circuit currents in d.c. auxiliary installations in power plants and substations, Part 1: calculation of short-circuit currents. This page is the engine's simplified engineering form of it, not a clause-by-clause reproduction.
- 2.Superposition: the total peak is the arithmetic sum of the source partial peaks and the total steady-state current the sum of the partial steady-state currents. The clause 3.1 combination / non-simultaneity correction factor is NOT applied, so the peak is conservative (higher) — the engine states this openly.
- 3.Source models: battery and RL DC source — Ik = Eb/(Rb+Rl), ip = Eb/Rb (peak limited by the internal resistance), τ = L/R, rise time t_r = 3τ. Smoothing capacitor group — closed-form RLC discharge, Ik,c = 0 (a capacitor carries no steady-state current) and the peak occurs at tp. Rectifier / DC machine entered as an explicit ikA / ipA placeholder.
- 4.Network and path: every source is reduced to an EMF plus a loop R and loop L; the cable loop between a source and the fault point is the minimum-resistance path found by Dijkstra on the DC cable graph (worst case). R and L are lumped; the DC short-circuit power uses the DC formula Ssc = Vnom · I (no √3).
- 5.Honest basis: a fault point that no source can reach has no partial current - it is shown as 'not available' rather than 0; when a source has no cable path to the fault point it is listed as a warning and excluded from the combination.
Short-circuit current per fault pointNot run yet — press Run. Nothing is invented while idle.
DC network input
Built-in example DC networkVnom 750 V · 3 busbar(s) · 2 cable(s)
Example DC network (built-in): a battery bank on the DC busbar plus a rectifier-fed DC source on the far combiner box, linked by two DC cables in series — so a short circuit on the busbar is fed through the cable loop and the superposed current really decays (κ = ip/Ik > 1). Every result value still comes from the engine; enter your own DC network on the Storage & DC page to replace it.
Fault points (engine input dcScOptions.faultPoints)
Not run yet — press Run. Nothing is invented while idle.
engine switch: the DC-network switch = true