Transformer load-rate / loss curve — quick reference

A quick loss-versus-loading reference: enter the transformer nameplate losses and the engine sweeps the load rate from no load to full load, returning iron, copper and total loss at every point. For temperature-rise criteria use /temp-rise; for the full thermal model use /thermal.

Method

Enter the transformer nameplate loss data and the engine sweeps the load rate from no load to full load, returning the no-load loss, load loss and total loss at every point. Both the curve and its breakdown are taken from the engine arrays.

Input sources

User input

Nameplate and system data entered by you.

Standard basis

Loss formula P=P0+Pk·(S/Sn)² and the rise model follow the selected standard

Engine result

Input and calculation

Enter the nameplate losses, then press Calculate; no-load loss and load loss are required — they are on the factory test report.

Standard basis
Standard selectable: IEC / GB / EN / GOST; loss and rise follow the selected standard (GB/T 1094.7 is a modified adoption of IEC 60076-7).

Transformer nameplate

Required
kVA
Range
Positive number
Default source
Example value, editable
Required
W
Range
Positive number
Default source
No default
Required
W
Range
Positive number
Default source
No default

Operating condition

Recommended
°C
Range
Positive number; may be left empty
Default source
Example value, editable
Recommended
kW
Range
Positive number; may be left empty
Default source
Example value, editable

Fill in the required values first - a missing value is never replaced by a default.

Results

Fill in the nameplate data above, press Run — losses, curves and efficiency appear here.

Basis and limits

Loss model: P_loss = P0 + Pk x (S/Sn)^2 (iron loss constant, copper loss proportional to the square of the load rate). P0 / Pk are taken from the values you enter; if you leave them blank the engine substitutes GB 20052-2020 grade-1 typical values.

The load-rate sweep is the engine evaluating the same loss model at 21 points between 0 and 100 %; the page only renders the returned array and adds no curve of its own.

Transformer efficiency η = P_out / (P_out + P_loss) is not output by the engine, so it shows "not available"; this page does not estimate it separately.

Sample case: a 1000 kVA transformer with the losses you enter produces the sweep shown; change any field and press 'Calculate' again.

Frequently asked questions
What can this calculator do?
Enter the transformer nameplate loss data Sn, P0 and Pk and the calculator sweeps the load rate from no load to full load, returning the iron loss, the copper loss and the total loss at every point, drawn as a curve together with the loss composition. The sweep follows the engine single loss model P_loss = P0 + Pk·(S/Sn)². Typical uses: showing why total loss grows faster than load, finding the loading at which copper loss overtakes iron loss, and reading the loss at the load rate you expect to run. Transformer efficiency is not output by the engine and is therefore shown as not available, never as zero.
How is the curve computed?
By evaluating the engine's single loss model P_loss = P0 + Pk·(S/Sn)² at successive load rates, with the iron loss constant and the copper loss following the square of the load rate. The curve and the composition are drawn from the engine array — the page does not run a second implementation of its own.
Why is the efficiency not shown?
Because the engine does not output it for this sweep: the page displays the quantities the engine really returns instead of deriving another one. The temperature-rise behaviour of the same transformer comes from the IEC 60076-7 model on the thermal pages, and anything the input cannot support is shown as not available.