ElecSimHub

Loss, temperature rise and core flux — engineering reference

A one-page engineering reference: enter one transformer nameplate and one series reactor fault condition; the engine returns the winding rise and hot-spot temperature with daily ageing, the loss split, and the reactor fault current with the core saturation characteristic. For criteria only use /temp-rise; for the loss curve only use /loss-curve.

Method

Enter the nameplate data of one transformer and the fault data of one series reactor. The engine returns the winding temperature rise and hot-spot temperature with the daily ageing, the loss split between iron and copper, and the reactor fault-current waveform together with the core saturation characteristic. Every figure carries its basis and standard, and anything the engine does not return is shown as "—", never as zero.

Input sources

User input

Nameplate and system data entered by you.

Standard basis

Rise, ageing and the reactor transient follow the selected standard; typical losses from GB 20052-2020

Engine result

Input and calculation

These inputs build an in-memory reference case for this page only. Nothing is written to your saved schemes and nothing is read from them. Tap position is preset to 0 % (the rated tap, the usual working position) and can be changed.

Standard basis
Rise and ageing follow the selected standard (IEC 60076-7 / GB/T 1094.7 …); the reactor fault current follows the selected short-circuit standard.

Transformer and load

Required
kVA
Range
Positive number
Default source
Example value, editable
Required
kW
Range
Positive number
Default source
Example value, editable
Required
Range
Positive number
Default source
Example value, editable
Recommended
W
Range
Positive number; may be left empty
Default source
No default
Recommended
W
Range
Positive number; may be left empty
Default source
No default
Recommended
%
Range
Positive number; may be left empty
Default source
Example value, editable
Recommended
°C
Range
Positive number; may be left empty
Default source
Example value, editable
Optional
%
Range
Positive number; may be left empty
Default source
Example value, editable

Reactor and fault condition

Required
kV
Range
Positive number
Default source
Example value, editable
Required
MVA
Range
Positive number
Default source
Example value, editable
Required
mH
Range
Positive number
Default source
Example value, editable
Required
A
Range
Positive number
Default source
Example value, editable
Recommended
Ω
Range
Positive number; may be left empty
Default source
Example value, editable
Optional
°
Range
Positive number; may be left empty
Default source
Example value, editable

Reactor saturation characteristic

Optional
Prefilled example values for demonstrating the saturation knee only — replace point by point with manufacturer data.
One point per line as "current A, inductance mH". Leave empty to get the linear section only — the engine then reports no saturation point and no flux-linkage peak instead of inventing one.

Required fields complete — ready to run.

Results

Not calculated yet — fill in the inputs on the left, press Run; the results appear here.

Basis and limits

Loss: P_loss = P0 + Pk·(S/Sn)² with S = P / cos φ; Q_loss = i0 %·Sn/100 + uk %·Sn/100·(S/Sn)². P0 and Pk are the values you entered, otherwise the GB 20052-2020 grade-1 typical values for that rating. All values follow the same engine loss model.

Temperature rise: Δθ_oil = 55·((1 + R·K²)/(1 + R))^0.8, Δθ_hs = Δθ_oil + 25·K^1.6, θh = θa + Δθ_hs with R = Pk/P0 and K = S/Sn — IEC 60076-7 oil-immersed ONAN exponential simplification. Relative ageing rate per the IEC 60076-7 §7.3 equivalent ageing factor F_AA = exp(15000/383 − 15000/(θh + 273)); daily life loss = Σ(V_i·Δt_i) / 24 h × 100 %.

Core flux: the loop equation L·di/dt = Um·sin(ωt + θ) − R·i is integrated with fixed-step RK4 using the flux linkage λ over the manufacturer λ–i characteristic as the state variable (piecewise-linear interpolation; no hysteresis, no eddy currents, no remanence). Short-circuit basis IEC 60076-7 (c = 1.1, Z_Q = Un²/Ssc, κ = 1.02 + 0.98·e^(−3R/X)); the saturation curve can only come from the manufacturer — IEC 60076-6 / GB/T 1094.6 provide no default one.

Reference case layout: one grid source, one two-winding transformer, one LV busbar and one static load, joined by three short cable sections of 10 m each (copper). The cable data does not drive the loss or temperature results - those come from P0/Pk and the loading only - but the sections must be present for the engine\'s load flow to run.

All values come from one engine pass: rise, ageing and the reactor transient follow the selected standard, loss allocation and the time-series load share the same engine model; this page only submits your input and presents what the engine returns.

Frequently asked questions
What can this calculator do?
Enter one transformer's nameplate data and one series reactor's fault data. The reference returns the loss split between iron and copper, the winding temperature rise and the hot-spot temperature together with the daily ageing, and the reactor fault-current waveform with the flux-linkage peak and the saturation knee. The thermal part uses the IEC 60076-7 oil-immersed exponential model (top-oil rise 55 K and hot-spot rise 80 K at rated load) driven by P0/Pk — your values first, otherwise the GB 20052-2020 grade-1 typical values for that rating. Typical uses: judging whether a loading profile is thermally acceptable, reading the daily ageing, and checking whether a reactor drives the core towards saturation during a fault. Missing data is shown as missing, never as zero.
Where do P0 and Pk come from when no nameplate value is entered?
Your entered values are used first; where they are absent the engine falls back to the GB 20052-2020 grade-1 typical values for that rating and discloses that the source is typical. A result is therefore never built silently on an assumed loss figure — the page tells you which basis it used.
What is the difference between the temperature rise and the daily ageing?
The temperature rise is the steady value above ambient (top-oil 55 K and hot-spot 80 K at rated load in the ONAN simplification); the daily ageing converts the hot-spot temperature into a relative ageing rate, which is what actually consumes transformer life. This page is a reference on a single equivalent thermal model, not a transient simulation and not a temperature-rise test.