Nameplate and system data entered by you.
Series reactor calculator
Current-limiting effect of a series reactor (IEC 60909): Ik with/without, reduction, terminal voltage, ±10% tolerance sweep.
Basis: IEC 60909 short circuit + time-domain RL integration (RK4); analytic vs numerical agree point-by-point within <1e-6. Saturation uses piecewise-linear interpolation of the manufacturer L–I curve; with no curve, no saturation point is invented.
Input sources
Formulas and limits come from the stated standard.
| Grid Ssc | Ik without | Ik with reactor | Reduction |
|---|---|---|---|
| 100 MVA | 6,351 A | 4,833 A | 23.9% |
| 200 MVA | 12,702 A | 7,801 A | 38.6% |
| 315 MVA | 20,005 A | 10,055 A | 49.7% |
| 500 MVA | 31,754 A | 12,352 A | 61.1% |
| 1000 MVA | 63,509 A | 15,334 A | 75.9% |
Basis: IEC 60909 simplified maximum short-circuit current — Ik = c·Un / (√3·(Zgrid + Zreactor)), c = 1.1; Zgrid = Un²/Ssc; Zreactor = 2πfL. Linear-inductance assumption; no lookup values.
⚠ The fault current is far above the rated current, so the iron core saturates deeply: the figures above are a conservative linear-inductance estimate. The real limiting effect requires the manufacturer L–I saturation curve — ask the reactor supplier for it.
Frequently asked questions
- What can this calculator do?
- Enter the system voltage, the grid short-circuit capacity S″kQ and the reactor inductance. The calculator computes the short-circuit current with and without the reactor from the IEC 60909 formula stated under the results, the current reduction in percent, the voltage that appears across the reactor during a fault, and sweeps the ±10% inductance tolerance so you can see a production-tolerance reactor. Typical uses: limiting the fault current seen by power-electronic converters (solid-state transformers, VFDs, PV/BESS inverters), smoothing converter current and damping high-frequency harmonics. Nothing is a lookup table.
- What is computed, and what is deliberately not a table?
- Everything comes from the IEC 60909 formula shown under the results: the loop impedance from the system voltage and the grid short-circuit capacity, the reactor reactance X = ωL in series with it, and the resulting current ratio. The ±10% tolerance is applied to the inductance L, not to the answer, so the sweep shows how a reactor at the edge of its tolerance behaves.
- Why is the voltage across the reactor reported?
- A series current-limiting reactor carries the full fault current, so the voltage across it during the fault (of the order of X·I″k) is what its own insulation and the downstream equipment have to withstand, and it also sets the voltage the converter sees once the fault is cleared. A reactor that limits the current well but is not rated for that voltage is the classic mis-application.