Series reactor calculator

Current-limiting effect of a series reactor (IEC 60909): Ik with/without, reduction, terminal voltage, ±10% tolerance sweep.

Method

Basis: IEC 60909 short circuit + time-domain RL integration (RK4); analytic vs numerical agree point-by-point within <1e-6. Saturation uses piecewise-linear interpolation of the manufacturer L–I curve; with no curve, no saturation point is invented.

Input sources

User input

Nameplate and system data entered by you.

Standard basis

Formulas and limits come from the stated standard.

Engine result

Reactor impedance ZL: 0.3142 ΩIk without reactor: 12,702 AIk with reactor: 7,801 AReduction: 38.6%Voltage across reactor: 4.24 kVIk / rated current: 52×
Reduction vs grid short-circuit capacity
Reduction vs grid short-circuit capacity
Grid SscIk withoutIk with reactorReduction
100 MVA6,351 A4,833 A23.9%
200 MVA12,702 A7,801 A38.6%
315 MVA20,005 A10,055 A49.7%
500 MVA31,754 A12,352 A61.1%
1000 MVA63,509 A15,334 A75.9%
Inductance tolerance sweep (±10%):0.9× L → 8,114 A1× L → 7,801 A1.1× L → 7,511 A
Fig 1 · Inductance vs limited fault current (L–Ik)Drawn directly from this page’s own results — 0 requests.
0.250.7511.52Ik0 without reactor
Limited current Ik (A)Ik0 without reactor
Inductance L (mH) → Limited current Ik (A)
Fig 2 · Grid short-circuit capacity vs current reduction
1002003155001000
Ik0 without reactorLimited current Ik (A)
Grid Ssc (MVA) → Ik (A)

Basis: IEC 60909 simplified maximum short-circuit current — Ik = c·Un / (√3·(Zgrid + Zreactor)), c = 1.1; Zgrid = Un²/Ssc; Zreactor = 2πfL. Linear-inductance assumption; no lookup values.

⚠ The fault current is far above the rated current, so the iron core saturates deeply: the figures above are a conservative linear-inductance estimate. The real limiting effect requires the manufacturer L–I saturation curve — ask the reactor supplier for it.

Frequently asked questions
What can this calculator do?
Enter the system voltage, the grid short-circuit capacity S″kQ and the reactor inductance. The calculator computes the short-circuit current with and without the reactor from the IEC 60909 formula stated under the results, the current reduction in percent, the voltage that appears across the reactor during a fault, and sweeps the ±10% inductance tolerance so you can see a production-tolerance reactor. Typical uses: limiting the fault current seen by power-electronic converters (solid-state transformers, VFDs, PV/BESS inverters), smoothing converter current and damping high-frequency harmonics. Nothing is a lookup table.
What is computed, and what is deliberately not a table?
Everything comes from the IEC 60909 formula shown under the results: the loop impedance from the system voltage and the grid short-circuit capacity, the reactor reactance X = ωL in series with it, and the resulting current ratio. The ±10% tolerance is applied to the inductance L, not to the answer, so the sweep shows how a reactor at the edge of its tolerance behaves.
Why is the voltage across the reactor reported?
A series current-limiting reactor carries the full fault current, so the voltage across it during the fault (of the order of X·I″k) is what its own insulation and the downstream equipment have to withstand, and it also sets the voltage the converter sees once the fault is cleared. A reactor that limits the current well but is not rated for that voltage is the classic mis-application.