DC short circuit — IEC 61660-1
Short-circuit current at the DC busbars of an auxiliary DC installation: the engine superposes the partial current of every DC source (battery bank, smoothing capacitor group, rectifier / DC machine given as an explicit current) over the minimum-resistance cable path, and reports the peak ip, the quasi-steady Ik, the ratio κ = ip/Ik, the loop time constant τ, the rise time and the DC short-circuit power for every selected fault point.
Pick a scheme first — then this column can calculate
This column runs the real engine on your project scheme, and there is none yet — that is why no calculation buttons are shown here (they are not broken). Start with any of the ways below; the fastest is the built-in example (one click, real parameters).
The studies in this column normally run on a whole scheme. If you only need one calculator-type function, you do not have to build a scheme.
10 kV incoming (200 MVA short-circuit level) → 1250 kVA transformer (Dyn11) → LV main switchboard → busbar → 5 feeders plus a fire/emergency ATS branch. 1000 kW calculated load, cosφ 0.85, power-factor target 0.95.
Load the real example scheme and start calculating →The scheme and its parameters go straight into your browser; replace the data with your own at any time.
Calculator mode computes the few outputs that only depend on parameters you type in yourself. Anything that genuinely needs the whole system (full-network load flow, coupling with other devices) is shown as “needs a scheme” and no number is given.
Nothing is pre-filled and nothing is invented: leave a required field empty and the result area says “unavailable”.
In the studio, place devices, wire them and pick models — that becomes your project scheme (drawings / BOM / report can be exported).
Open the studio →Use the chat bubble bottom-right, or Contact us — we will set the example to your site parameters.
Note: every number comes from the engine. With no scheme, nothing is invented here.
Frequently asked questions
- What can this calculator do?
- Enter the DC network — nominal voltage, busbars, cable sections and lengths and the DC sources (battery bank, smoothing capacitor, rectifier or DC machine) — and choose the fault points. For each point the engine superposes the partial current of every DC source over the minimum-resistance cable path and returns the peak current ip, the quasi-steady current Ik, the ratio κ = ip/Ik, the loop time constant τ, the rise time 3τ, the time to peak and the DC short-circuit power, with a per-source contribution table, a time-current decay chart and a network sketch. Typical uses: rating DC switchgear and busbars, checking a battery-bank installation, and showing which source contributes most at a given fault point. Missing data is shown as missing, never as zero.
- Which standard and which model are behind the numbers?
- IEC 61660-1 in its simplified engineering form: the partial currents are superposed arithmetically, ip = Σ ip,s and Ik = Σ Ik,s, without the clause 3.1 correction factor; R and L are lumped and the cable loop is the minimum-resistance path found by Dijkstra, i.e. the worst case. No arc-voltage model, no power-electronic current limiting and no IEC 61660-2 mechanical or thermal effects are included, and the page states this.
- Why is a per-source contribution table shown?
- Because the total peak depends on which sources actually reach the fault point: the table gives each source's model, ip,s, Ik,s, κs, loop R and L and the path, so you can see that a fault away from the battery is fed mainly through the cable loop and that the superposed current really decays. A source that cannot reach the point contributes nothing and is reported as unavailable, not as zero.