ElecSimHub

Series reactor — current-limiting calculator

Enter the system voltage, the grid short-circuit capacity and the reactor inductance: you get the short-circuit current with and without the reactor, the reduction, the voltage that appears across the reactor during a fault, and the effect of the ±10% inductance tolerance. Everything is computed from the IEC 60909 formula stated under the results — nothing is a lookup table.

Reactor impedance ZL: 0.3142 ΩIk without reactor: 12,702 AIk with reactor: 7,801 AReduction: 38.6%Voltage across reactor: 4.24 kVIk / rated current: 52×
Reduction vs grid short-circuit capacity
Grid SscIk withoutIk with reactorReduction
100 MVA6,351 A4,833 A23.9%
200 MVA12,702 A7,801 A38.6%
315 MVA20,005 A10,055 A49.7%
500 MVA31,754 A12,352 A61.1%
1000 MVA63,509 A15,334 A75.9%
Inductance tolerance sweep (±10%):0.9× L → 8,114 A1× L → 7,801 A1.1× L → 7,511 A

Basis: IEC 60909 simplified maximum short-circuit current — Ik = c·Un / (√3·(Zgrid + Zreactor)), c = 1.1; Zgrid = Un²/Ssc; Zreactor = 2πfL. Linear-inductance assumption; no lookup values.

⚠ The fault current is far above the rated current, so the iron core saturates deeply: the figures above are a conservative linear-inductance estimate. The real limiting effect requires the manufacturer L–I saturation curve — ask the reactor supplier for it.

Where it is used: series reactors are placed in front of power-electronic converters (solid-state transformers, VFDs, PV/BESS inverters) to smooth the converter current, damp high-frequency harmonics and — most importantly — limit the fault current that would otherwise destroy the semiconductor switches.